Ex ZS 73 S
Features/Options
- Ex zone 1 and 21
- Metal enclosure
- 2 contacts
- Wire length up to 2 x 100 m
- Release by push button (VD)
- Available without unlocking mechanism (per DIN EN 60947-5-1)
- Wire pull and breakage detection
- Special version only for dust Ex zone 22
- N.B.: Please state required approvals for Russia, China, Brazil and North America with your order!
Product image

Technical data
| Standards | EN 60947-5-1, -5; EN 60079-0, EN 60079-1, EN 60079-31; EN ISO 13849-1 |
|---|---|
| Enclosure | aluminium die-cast, enamel finish |
| Cover | glass-fibre reinforced, shock-proof thermoplastic, ultramid |
| Switch insert | Ex 14 |
| Degree of protection | IP 65 to IEC/EN 60529 |
| Contact material | silver |
| Switching system | slow action, positive break NC contacts ![]() |
| Switching elements | change-over contact with double break or 2 NC contacts |
| Connection | cable H05VV-F |
| Cable section | 4 x 0.75 mm2 (incl. conductor ferrules) |
| Cable length | 3 m |
| B10d (10% Load) | Ex ZS 73 S: 2 million Ex ZS 73 S VD: 200.000 |
| TM | max. 20 years |
| Uimp | 4 kV |
| Ui | 250 V |
| Ithe | T6: 6 A, T5: 3 A |
| Utilisation category | AC-15, DC-13 |
| Ie/Ue | 6 A/250 VAC, 0.25 A/230 VDC |
| Max. fuse rating | 6 A gL/gG D-fuse |
| Ambient temperature | T6: –20 °C … +65 ºC; T5: –20 °C … +90 ºC |
| Mechanical life | Ex ZS 73 S: > 1 million operations Ex ZS 73 S VD: > 100.000 operations |
| Max. wire length | 2 x 100 m |
| Features | wire pull and breakage detection |
| Ex certification | II 2G Ex d IIC T6/T5 Gb, II 2D Ex tb IIIC T80°C/T95°C Db IP65 IECEx Ex d IIC T6/T5 Gb, Ex tb IIIC T80°C/T95°C Db IP65 |
| Approvals | PTB 11 ATEX 1003 X, IECEx PTB 07.0034 X ![]() |






II 2G Ex d IIC T6/T5 Gb,